Skip to content

Rainwater and firewater storage — can one tank serve both purposes?

There is room for one large tank on the site. It needs to collect water from the roof, supply irrigation and provide a firefighting reserve. The idea seems straightforward, but each function requires something different: available water, the ability to use it, or empty space for the next rainfall.

Systems combining these functions can be designed. Examples of existing installations are described in the Berliner Regenwasseragentur database. Whether a solution is suitable for a particular site in Poland, however, depends on its requirements, design and applicable regulations. Connecting a downpipe to a tank does not resolve the whole question. Wisch Engineering installation example.

Horizontal steel tank on supports with a connection on the front end
A tank from the Agrotex range. The photograph does not show a combined rainwater and firewater installation.

Three functions, three different needs

A “rainwater tank” may store water for later use or temporarily accommodate heavy runoff. In the second case, how the tank empties also matters. Manufacturer Mall describes detention tanks as temporary storage systems with a restricted outlet, intended to reduce the load on the receiving drainage system or watercourse. How Mall detention tanks work.

The table below explains the different functions. It is not a layout for dividing a particular tank.

Function What needs to be available? What needs to be resolved?
Firefighting reserve Water intended for withdrawal during a fire How will the required reserve and access to it be maintained?
Everyday rainwater use Water that can be consumed, for example for irrigation Down to what level can water be withdrawn?
Accommodating heavy rainfall Empty space for incoming water How will that space be available before the next rainfall, and where will excess water go?

A simple relationship follows: space already occupied by water cannot receive more without an outflow. Withdrawing water creates empty space, but reduces the reserve. The same cubic metres cannot simultaneously be counted as permanently stored water and empty capacity waiting for heavy rain.

Rainwater as a source and a shared reserve

Two questions need to be considered separately. First: where does the water entering the tank come from? Second: what can the stored water be used for? Filling a tank with rainwater and subsequently using that water for several purposes are separate design decisions.

During dry weather, inflow from the roof stops. The design concept therefore needs to explain how the required reserve will be maintained and replenished after withdrawal. Forecast rainfall is not water already in the tank. This is a water balance constraint, regardless of the material used for the tank walls.

It helps to consider three scenarios: a dry period with everyday consumption, heavy rainfall when the water level is already high, and withdrawal for firefighting. For each, it should be clear where water enters, where it leaves and how much remains. Only then can the compatibility of the intended functions be assessed.

What do Polish regulations say?

For water supplies used in external firefighting, the Polish regulation of 24 July 2009 is a relevant starting point. In specified circumstances, Section 6 provides for the use of water resources that also serve other needs and process tanks adapted for firefighting withdrawal. This does not mean that any rainwater tank is acceptable. Polish regulation — Section 6.

A building’s internal firefighting water supply system needs to be considered separately. For example, Section 24(2) of the Polish regulation on fire protection of buildings and other premises concerns buildings in Poland’s “high” and “high-rise” categories and a reserve dedicated exclusively to the stated purpose. This specific provision is not a rule for every tank. Sprinkler installations also require their own assessment; their rules should not automatically be applied to every external firefighting arrangement. Polish regulation — Chapter 5, Section 24.

How can the functions be separated?

An interesting example comes from the Wisch Engineering site in Berlin. According to the description provided by those involved in the project, the tanks combine firefighting water storage, rainwater use within the building and capacity for increased rainfall inflow. This is a German project example, not a basis for approving an equivalent arrangement in Poland. Project description.

For your own site, discuss with the designer how these functions might be separated: individual tanks, compartments or an appropriately designed withdrawal and control arrangement. Each concept also needs to be assessed during faults, cleaning and shutdown of part of the installation. A user’s promise to “leave some water” when irrigating does not describe how the system operates.

Specific questions are a useful starting point. What will stop everyday withdrawal at the boundary of the reserved volume? How will a low water level be detected? What happens during a power failure or if the outlet becomes blocked? The answers help assess the concept without assigning arbitrary percentages of the tank’s capacity to different uses.

What else should the design address?

Beyond the capacity balance, there are questions about how water enters and leaves the system. Will the tank receive only roof runoff, or water from a yard as well? What treatment is planned before the inlet? How will the tank and its connections be protected during freezing weather? How can sediment be removed and inspections carried out while maintaining the site’s required fire protection?

These questions help compare a combined arrangement with separate tanks. A single tank body may take up less space, but the associated installation, maintenance access and consequences of a temporary shutdown also need to be assessed.

Horizontal steel tank inside a workshop
The tank body is one part of the system; its water supply, draw-off and controls also need to be designed.

Establish the functions before choosing the tank size

When considering a 50 m³ steel water tank, keep this distinction in mind: listing two possible applications in an offer does not confirm that the tank is ready to perform both simultaneously.

One tank can form part of a more complex water management system. Whether combining functions makes sense depends on having both the right water reserve and the necessary space for incoming water available when required. The capacity stated in a catalogue is just one of the inputs to that assessment.